ITB-h Power Transformer Integrated Test Bench According With The Relevant Standard Iec60076-3. Our Transformer Integrated Test Bench Mainly Do The No-load Characteristics And Load Characteristics Of Power Transformer And Distribution Transformer Test, The Frequency Multiplication Inducted Withstand Voltage Test And Power Frequency Withstand Voltage Test. The Measuring Device Is Controlled By The High-grade Single Chip Microcomputer (scm), With The Digital Display, The No Load, Short Circuit And Other Test Data Synchronously Also Sampled By The Scm. It Is Avoid Separately Reading The Voltmeter, Ammeter And Power Meter In The Traditional Test Methods And Causing Error Due To Manual Computation.

 

 

Product Characteristics

 

1.The Power Transformer Integrated Test Bench Use A Large Backlight Lcd For Display, The Operation And Display Classification Being Clear And Easy.

 

2.It Can Meet The Dc Resistance Test, Transformation Ratio & Group Test, No-load Loss Test, Load Loss Test, Ac Withstand Voltage Test, Induced Withstand Voltage Test, Etc. Of Power Transformers Which The Capaticy No More Than 2,500kva And The Voltage No More Than 220kv.

 

3.Voltage And Current Value Can Be Read From The Data Display Meter Or Pointer Meter Directly, And The Test Result Of Loss, Transformation  Ratio And Dc Resistance Can Be Printed Out Directly.

 

4.It Has The Overcurrent Sound-light Alarm Alarm And Timekeeping Function For The Withstand Voltage Test.

 

Specification

 

1. Voltage : 0.1-600V, relative error: ±(0.2% reading + 0.1% range)

2. Current : 0.1-200A, relative error:±(0.2% reading + 0.1% range)

3. Power: U*I, relative error: ±(0.2% reading + 0.1% range)

4. Power factor : relative error, 0.1-0.9999±3d

5. Power supply: AC220V±10%, 50Hz±2%

6. Operating condition

Working temperature range: 0-40℃; Relative humidity 30%-90%

7. Dimension: Customization

8. Weight: Customization

 